Friedrich X-STAR R-410A Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Climatiseurs à système divisé Friedrich X-STAR R-410A. Friedrich X-STAR R-410A User's Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - Room Air Conditioners

Service ManualR-410A ModelsRoom Air Conditioners 2010X-Star-ServMan (4-10) 115-Volt: XQ05M10A, XQ06M10A, XQ08M10A, XQ10M10ACool Only115-Volt: EQ

Page 2 - Table Of Contents

To startunitsiti,elc at pec erreporpaotnideggulpdnadellatsnisirenoitidnocriaruoyfIready to go.The firsttimethe unit is started, thecompressorwilldelay

Page 3 - IMPORTANT SAFETY INFORMATION

To set the timerNOTE: You can set the START and STOP times a minimum of one hourapart, and a maximum of 23 hours apart.9TIMER START - Press Start .gni

Page 4 - MECHANICAL HAZARDS:

MODE CONTROLThe mode control pad(s) allow the selection of the operating modes of the unit.There is a two second delay before the mode activates its a

Page 5 - INTRODUCTION

MECHANICAL COMPONENTSPlenum assembly Diffuser with directional louvers used to direct the conditioned airfl ow.Blower wheel Attaches to the indoor si

Page 6 - X Q 08 M 1 0 A

13TESTING THE ELECTRONIC CONTROL BOARDS FOR XQ MODELS Activating Test Mode: Activate test mode by pressing at the same time the “MODE” button and th

Page 7 - PERFORMANCE DATA

TEST: 1. Remove leads from thermostat.2. Turn thermostat knob clockwise to its coldest position.3. Test for continuity between the two termin

Page 8 - ELECTRICAL DATA

CAPACITORS ELECTRIC SHOCK HAZARD WARNINGTurn off electric power before servicing. Discharge capacitor with a 20,000 Ohm 2 Watt resistor before handlin

Page 9 - Figure 1

HEATING ELEMENT (See Figure)All electric heat models are equipped with a heating element. The EQ08 has a 1.15 KW element. The heating element contain

Page 10 - (XQmodels)

Suction Line Evaporator Coil Metering Device Refrigerant Strainer Discharge Line Condenser Coil Compressor Refrigerant Drier Liquid Line A

Page 11 - How to use the remote control

• R-410A pressure is approximately 60% higher than R-22 pressure.• R-410A cylinders must not be allowed to exceed 125 F, they may leak or rupture.•

Page 12

1Table Of Contents Important Safety Information ...

Page 13

Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performan

Page 14 - COMPONENTS TESTING

3. Install a process tube to sealed system. 4. Make necessary repairs to system. 5. Evacuate system to 200 microns or less. 6. Weigh in refrig

Page 15 - 4th and 5th and 6th and 7th

Undercharged Refrigerant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and coo

Page 16 - Capacitor Connections

Restricted Refrigerant System Troubleshooting a restricted refrigerant system can be difcult. The following procedures are the more common prob

Page 17 - ELECTRIC SHOCK HAZARD

Locked Rotor Voltage (L.R.V.) Test Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition. Single P

Page 18

Single Phase Resistance Test Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1). Touch the leads of the

Page 19

Recommended procedure for compressor replacement 1. Be certain to perform all necessary electrical and refrigeration tests to be sure

Page 20 - Refrigerant Charging

1.2.3.4.5.ELECTRIC SHOCK HAZARD WARNINGTurn off electric power before service or installation.Failure to do so may result in personal injury, or death

Page 21 - Method Of Charging / Repairs

ROUTINE MAINTENANCE AIR FILTER Clean the unit air intake lter at least every 300 to 350 hours of operation. Clean the lters with a mild detergent i

Page 22

SLEEVE / DRAIN Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both a

Page 23

IMPORTANT SAFETY INFORMATIONThe information contained in this manual is intended for use by a qualied service technician wh

Page 24 - COMPRESSOR CHECKS

ROOM AIR CONDITIONER UNIT PERFORMANCE TEST DATA SHEETDATE: _______________ MODEL:_______________ SERIAL:________________ YES

Page 25 - Single Phase Resistance Test

Problem Possible Cause Possible SolutionUnit does not operate. The unit is turned to the off position, Turn the unit to the on position and raise or

Page 26 - COMPRESSOR REPLACEMENT

Unit Does Not Cool/Heat On And Off Too Frequently (continued). The outside temperature is below 60° F (16° C). Do not try to operate your air conditi

Page 27

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS noitcA esuaC elbissoP melborPCompressordoes not run Low voltage Check voltage at compress

Page 28 - ROUTINE MAINTENANCE

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS noitcA esuaC elbissoP melborPUnit does not run Fuse blown or circuit tripped Replace fus

Page 29

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS noitcA esuaC elbissoP melborPCompressor runs for short periods only. Cycles on overload

Page 30 - PERFORMANCE TEST DATA SHEET

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS noitcA esuaC elbissoP melborPWater “spitting” into room Sublimation:When unconditioned s

Page 31 - GENERAL TROUBLESHOOTING TIPS

HEAT / COOL ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS noitcAesuaC elbissoPmelborPRoom temperature uneven (Heating cycle)Heat anticipator (resi

Page 32

ELECTRONIC CONTROLCOOL ONLY MODELS:XQ05M10A XQ06M10A XQ08M10A XQ10M10A37

Page 33

ELECTROMECHANICAL CONTROLCOOL WITH ELECTRIC HEAT MODEL:EQ08M11A38

Page 34

Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, •and sleeve on the room side of the air co

Page 35

4INSTRUCTIONS FOR USING COOLING LOAD ESTIMATEFORM FOR ROOM AIR CONDITIONERS(AHAM PUB. NO. RAC-1)A. This cooling load estimate form is suitable for es

Page 36

5COOLING LOAD ESTIMATE FORMHEAT GAIN FROM1. WINDOWS: Heat gain from the sun. Northeast East Southeast South Southwest West Northwest North2.

Page 37

6Following is an example using the heat load form:A space to be conditioned is part of a house geographically located in an area where the lowest outd

Page 38 - COOL ONLY MODELS:

7HEATING LOAD FORMFRIEDRICH ROOM UNIT HEAT PUMPS BTU/HR PERWALLS: (Linear Feet) °F TEMP. DIFFERENCE 2” Insulation Lin. Ft. x 1.6 Average Lin.

Page 39 - EQ08M11A

43Friedrich Air Conditioning CompanyP.O. Box 1540 San Antonio, TX 78295210.357.4400www.friedrich.comROOM AIR CONDITIONERSLIMITED WARRANTYFIRST YEARANY

Page 40 - (AHAM PUB. NO. RAC-1)

FRIEDRICH AIR CONDITIONING CO. Post Ofce Box 1540 · San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212 (210) 35

Page 42 - HEAT LOAD FORM

X-Star-ServMan (4-10) FRIEDRICH AIR CONDITIONING CO. Post Ofce Box 1540 · San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway · San Antonio, Te

Page 43 - HEATING LOAD FORM

System ControlsReturn Air Grille/FilterCondenser Fan BladeLiquid Filter DriersCompressorCondenser CoilDischarge AirOutdoor GrilleSleeveBasepanBlower M

Page 44 - LIMITED WARRANTY

Serial Number Decade Manufactured L=0 C=3 F=6 J=9 A=1 D=4 G=7 B=2 E=5 H=8 A K A R 00001 Production Run Number Year Ma

Page 45 - CONTACT INFORMATION

PERFORMANCE DATACOOLING PERFORMANCE DATA*EVAP. AIR TEMP. DEG. FCONDENSER TEMPERATURE DEG. FDischarge Temp Suction Temp Super Heat Sub-CoolingOPERATING

Page 46

ELECTRICAL DATAELECTRIC SHOCK HAZARD WARNINGTurn off electric power before service or installation.All electrical connections and wiring MUST be

Page 47 - Printed in the U.S.A

ELECTRICAL SHOCK HAZARD WARNINGMake sure your electrical receptacle has the same configuration as your air conditioner’s plug. If different, consult a

Commentaires sur ces manuels

Pas de commentaire